Id Date Time Event 100000 07/19/03 15:08:00 *** PowerChute PLUS Version 5.0 Started *** 100200 07/19/03 15:08:13 Communication established 200002 07/22/03 13:14:13 UPS on battery: Brownout 200.0 V 100300 07/22/03 13:14:13 Normal power restored: UPS on line 200002 07/22/03 13:14:19 UPS on battery: Brownout 201.9 V 100300 07/22/03 13:14:19 Normal power restored: UPS on line 200001 07/22/03 13:14:20 UPS on battery: High input line voltage 243.1 V 100300 07/22/03 13:14:20 Normal power restored: UPS on line 200001 07/22/03 13:14:22 UPS on battery: High input line voltage 244.9 V 100300 07/22/03 13:14:22 Normal power restored: UPS on line 300301 07/29/03 07:54:33 UPS battery is discharged: 100.0 100701 07/29/03 07:54:35 UPS returned from low battery condition: 100.0 100403 07/31/03 07:51:45 Self-test at UPS passed 300301 08/05/03 07:41:01 UPS battery is discharged: 100.0 100701 08/05/03 07:41:01 UPS returned from low battery condition: 100.0 300301 08/05/03 10:00:41 UPS battery is discharged: 100.0 100701 08/05/03 10:00:43 UPS returned from low battery condition: 100.0 300301 08/05/03 11:21:36 UPS battery is discharged: 100.0 100701 08/05/03 11:21:36 UPS returned from low battery condition: 100.0 300301 08/08/03 07:39:57 UPS battery is discharged: 100.0 100701 08/08/03 07:39:59 UPS returned from low battery condition: 100.0 300301 08/11/03 17:04:55 UPS battery is discharged: 100.0 100701 08/11/03 17:04:57 UPS returned from low battery condition: 100.0 300301 08/13/03 20:36:03 UPS battery is discharged: 100.0 100701 08/13/03 20:36:04 UPS returned from low battery condition: 100.0 100403 08/14/03 07:51:32 Self-test at UPS passed 200000 08/21/03 20:20:12 UPS on battery 100300 08/21/03 20:20:13 Normal power restored: UPS on line 200001 08/21/03 20:23:00 UPS on battery: High input line voltage 243.1 V 100300 08/21/03 20:23:01 Normal power restored: UPS on line 300301 08/24/03 10:30:17 UPS battery is discharged: 100.0 100701 08/24/03 10:30:18 UPS returned from low battery condition: 100.0 300301 08/24/03 13:16:04 UPS battery is discharged: 100.0 100701 08/24/03 13:16:05 UPS returned from low battery condition: 100.0 300301 08/25/03 23:18:08 UPS battery is discharged: 100.0 100701 08/25/03 23:18:10 UPS returned from low battery condition: 100.0 100403 08/28/03 07:52:17 Self-test at UPS passed 300301 08/28/03 21:23:32 UPS battery is discharged: 100.0 100701 08/28/03 21:23:33 UPS returned from low battery condition: 100.0 300301 09/09/03 19:36:36 UPS battery is discharged: 100.0 100701 09/09/03 19:36:37 UPS returned from low battery condition: 100.0 100403 09/11/03 07:52:05 Self-test at UPS passed 300301 09/12/03 14:11:22 UPS battery is discharged: 100.0 100701 09/12/03 14:11:24 UPS returned from low battery condition: 100.0 300301 09/14/03 02:35:16 UPS battery is discharged: 100.0 100701 09/14/03 02:35:17 UPS returned from low battery condition: 100.0 300301 09/16/03 09:40:38 UPS battery is discharged: 100.0 100701 09/16/03 09:40:38 UPS returned from low battery condition: 100.0 300301 09/16/03 11:23:15 UPS battery is discharged: 100.0 100701 09/16/03 11:23:16 UPS returned from low battery condition: 100.0 300301 09/23/03 12:46:34 UPS battery is discharged: 100.0 100701 09/23/03 12:46:36 UPS returned from low battery condition: 100.0 300301 09/23/03 15:48:33 UPS battery is discharged: 100.0 100701 09/23/03 15:48:34 UPS returned from low battery condition: 100.0 100403 09/25/03 07:52:53 Self-test at UPS passed 300301 09/26/03 22:26:17 UPS battery is discharged: 100.0 100701 09/26/03 22:26:17 UPS returned from low battery condition: 100.0 300301 09/26/03 22:26:17 UPS battery is discharged: 100.0 100701 09/26/03 22:26:18 UPS returned from low battery condition: 100.0 300301 09/26/03 22:26:18 UPS battery is discharged: 100.0 100701 09/26/03 22:26:18 UPS returned from low battery condition: 100.0 300301 09/26/03 22:26:19 UPS battery is discharged: 100.0 100701 09/26/03 22:26:19 UPS returned from low battery condition: 100.0 300301 09/26/03 22:26:19 UPS battery is discharged: 100.0 100701 09/26/03 22:26:20 UPS returned from low battery condition: 100.0 100100 09/28/03 21:14:00 *** PowerChute PLUS Stopped *** 100000 11/11/03 04:53:09 *** PowerChute PLUS Version 5.0 Started *** 100200 11/11/03 04:53:22 Communication established 300301 11/11/03 10:33:50 UPS battery is discharged: 100.0 100701 11/11/03 10:33:52 UPS returned from low battery condition: 100.0 300301 11/11/03 11:48:02 UPS battery is discharged: 100.0 100701 11/11/03 11:48:04 UPS returned from low battery condition: 100.0 300301 11/12/03 14:45:19 UPS battery is discharged: 100.0 100701 11/12/03 14:45:19 UPS returned from low battery condition: 100.0 300301 11/12/03 15:41:40 UPS battery is discharged: 100.0 100701 11/12/03 15:41:41 UPS returned from low battery condition: 100.0 300301 11/12/03 15:41:41 UPS battery is discharged: 100.0 100701 11/12/03 15:41:41 UPS returned from low battery condition: 100.0 300301 11/12/03 15:41:42 UPS battery is discharged: 100.0 100701 11/12/03 15:41:42 UPS returned from low battery condition: 100.0 300301 11/12/03 15:41:42 UPS battery is discharged: 100.0 100701 11/12/03 15:41:42 UPS returned from low battery condition: 100.0 300301 11/12/03 15:41:43 UPS battery is discharged: 100.0 100701 11/12/03 15:41:43 UPS returned from low battery condition: 100.0 300301 11/12/03 15:41:43 UPS battery is discharged: 100.0 100701 11/12/03 15:41:44 UPS returned from low battery condition: 100.0 300301 11/12/03 15:41:44 UPS battery is discharged: 100.0 100701 11/12/03 15:41:44 UPS returned from low battery condition: 100.0 300301 11/12/03 15:41:45 UPS battery is discharged: 100.0 100701 11/12/03 15:41:45 UPS returned from low battery condition: 100.0 300301 11/13/03 12:15:52 UPS battery is discharged: 100.0 100701 11/13/03 12:15:54 UPS returned from low battery condition: 100.0 300301 11/14/03 15:06:44 UPS battery is discharged: 100.0 100701 11/14/03 15:06:44 UPS returned from low battery condition: 100.0 300301 11/14/03 15:06:44 UPS battery is discharged: 100.0 100701 11/14/03 15:06:45 UPS returned from low battery condition: 100.0 300301 11/14/03 15:06:45 UPS battery is discharged: 100.0 100701 11/14/03 15:06:45 UPS returned from low battery condition: 100.0 300301 11/14/03 15:06:46 UPS battery is discharged: 100.0 100701 11/14/03 15:06:46 UPS returned from low battery condition: 100.0 300301 11/14/03 15:06:46 UPS battery is discharged: 100.0 100701 11/14/03 15:06:46 UPS returned from low battery condition: 100.0 300301 11/14/03 15:06:47 UPS battery is discharged: 100.0 100701 11/14/03 15:06:47 UPS returned from low battery condition: 100.0 300301 11/14/03 17:18:08 UPS battery is discharged: 100.0 100701 11/14/03 17:18:10 UPS returned from low battery condition: 100.0 300301 11/16/03 09:18:43 UPS battery is discharged: 100.0 100701 11/16/03 09:18:43 UPS returned from low battery condition: 100.0 300301 11/16/03 09:18:44 UPS battery is discharged: 100.0 100701 11/16/03 09:18:44 UPS returned from low battery condition: 100.0 300301 11/17/03 21:17:03 UPS battery is discharged: 100.0 100701 11/17/03 21:17:04 UPS returned from low battery condition: 100.0 300301 11/18/03 13:48:14 UPS battery is discharged: 100.0 100701 11/18/03 13:48:14 UPS returned from low battery condition: 100.0 300301 11/18/03 13:48:15 UPS battery is discharged: 100.0 100701 11/18/03 13:48:15 UPS returned from low battery condition: 100.0 300301 11/18/03 13:48:15 UPS battery is discharged: 100.0 100701 11/18/03 13:48:16 UPS returned from low battery condition: 100.0 300301 11/18/03 13:48:16 UPS battery is discharged: 100.0 100701 11/18/03 13:48:16 UPS returned from low battery condition: 100.0 300301 11/18/03 13:48:16 UPS battery is discharged: 100.0 100701 11/18/03 13:48:17 UPS returned from low battery condition: 100.0 300301 11/18/03 13:48:17 UPS battery is discharged: 100.0 100701 11/18/03 13:48:17 UPS returned from low battery condition: 100.0 300301 11/19/03 08:59:23 UPS battery is discharged: 100.0 100701 11/19/03 08:59:24 UPS returned from low battery condition: 100.0 300301 11/19/03 08:59:24 UPS battery is discharged: 100.0 100701 11/19/03 08:59:24 UPS returned from low battery condition: 100.0 300301 11/19/03 08:59:24 UPS battery is discharged: 100.0 100701 11/19/03 08:59:25 UPS returned from low battery condition: 100.0 300301 11/19/03 08:59:25 UPS battery is discharged: 100.0 100701 11/19/03 08:59:25 UPS returned from low battery condition: 100.0 300301 11/19/03 08:59:26 UPS battery is discharged: 100.0 100701 11/19/03 08:59:26 UPS returned from low battery condition: 100.0 100403 11/20/03 06:53:39 Self-test at UPS passed 100100 11/22/03 03:38:27 *** PowerChute PLUS Stopped *** 100000 11/22/03 03:44:49 *** PowerChute PLUS Version 5.0 Started *** 100200 11/22/03 03:45:01 Communication established 100100 11/22/03 03:45:38 *** PowerChute PLUS Stopped *** 100000 11/22/03 03:48:27 *** PowerChute PLUS Version 5.0 Started *** 100200 11/22/03 03:48:40 Communication established 100100 11/22/03 03:49:30 *** PowerChute PLUS Stopped *** 100000 11/22/03 04:06:57 *** PowerChute PLUS Version 5.0 Started *** 100200 11/22/03 04:07:09 Communication established 100100 11/22/03 04:07:55 *** PowerChute PLUS Stopped *** 100000 11/22/03 05:18:47 *** PowerChute PLUS Version 5.0 Started *** 100200 11/22/03 05:18:59 Communication established 100100 11/22/03 05:19:23 *** PowerChute PLUS Stopped *** 100000 12/06/03 12:59:30 *** PowerChute PLUS Version 5.0 Started *** 100200 12/06/03 12:59:43 Communication established 300301 12/06/03 16:51:53 UPS battery is discharged: 100.0 100701 12/06/03 16:51:55 UPS returned from low battery condition: 100.0 100100 12/07/03 15:23:39 *** PowerChute PLUS Stopped *** 100000 12/07/03 15:32:34 *** PowerChute PLUS Version 5.0 Started *** 100200 12/07/03 15:32:46 Communication established 100100 12/07/03 21:48:45 *** PowerChute PLUS Stopped *** 100000 12/07/03 21:51:25 *** PowerChute PLUS Version 5.0 Started *** 100200 12/07/03 21:51:38 Communication established 100100 12/07/03 21:58:41 *** PowerChute PLUS Stopped *** 100000 12/31/03 21:07:37 *** PowerChute PLUS Version 5.0 Started *** 100200 12/31/03 21:07:50 Communication established 100100 12/31/03 21:14:51 *** PowerChute PLUS Stopped *** 100000 01/14/04 14:50:49 *** PowerChute PLUS Version 5.0 Started *** 100200 01/14/04 14:51:02 Communication established 100403 01/15/04 06:55:43 Self-test at UPS passed 300301 01/15/04 16:32:20 UPS battery is discharged: 100.0 100701 01/15/04 16:32:22 UPS returned from low battery condition: 100.0 300301 01/16/04 08:45:25 UPS battery is discharged: 100.0 100701 01/16/04 08:45:25 UPS returned from low battery condition: 100.0 300301 01/16/04 08:45:26 UPS battery is discharged: 100.0 100701 01/16/04 08:45:26 UPS returned from low battery condition: 100.0 300301 01/16/04 08:45:26 UPS battery is discharged: 100.0 100701 01/16/04 08:45:27 UPS returned from low battery condition: 100.0 300301 01/16/04 08:45:34 UPS battery is discharged: 100.0 100701 01/16/04 08:45:34 UPS returned from low battery condition: 100.0 300301 01/16/04 08:45:35 UPS battery is discharged: 100.0 100701 01/16/04 08:45:35 UPS returned from low battery condition: 100.0 300301 01/16/04 08:45:35 UPS battery is discharged: 100.0 100701 01/16/04 08:45:36 UPS returned from low battery condition: 100.0 300301 01/16/04 08:45:36 UPS battery is discharged: 100.0 100701 01/16/04 08:45:37 UPS returned from low battery condition: 100.0 300301 01/16/04 08:45:37 UPS battery is discharged: 100.0 100701 01/16/04 08:45:37 UPS returned from low battery condition: 100.0 300301 01/16/04 08:45:38 UPS battery is discharged: 100.0 100701 01/16/04 08:45:38 UPS returned from low battery condition: 100.0 300301 01/16/04 08:45:38 UPS battery is discharged: 100.0 100701 01/16/04 08:45:39 UPS returned from low battery condition: 100.0 300301 01/16/04 08:45:39 UPS battery is discharged: 100.0 100701 01/16/04 08:45:39 UPS returned from low battery condition: 100.0 300301 01/16/04 08:45:40 UPS battery is discharged: 100.0 100701 01/16/04 08:45:40 UPS returned from low battery condition: 100.0 300301 01/28/04 19:16:42 UPS battery is discharged: 100.0 100701 01/28/04 19:16:44 UPS returned from low battery condition: 100.0 300301 01/29/04 00:56:58 UPS battery is discharged: 100.0 100701 01/29/04 00:56:59 UPS returned from low battery condition: 100.0 100403 01/29/04 06:55:30 Self-test at UPS passed 300301 02/03/04 16:56:58 UPS battery is discharged: 100.0 100701 02/03/04 16:56:59 UPS returned from low battery condition: 100.0 300301 02/03/04 17:19:37 UPS battery is discharged: 100.0 100701 02/03/04 17:19:38 UPS returned from low battery condition: 100.0 100403 02/12/04 06:56:18 Self-test at UPS passed 100403 02/26/04 06:57:01 Self-test at UPS passed 300301 02/27/04 15:40:41 UPS battery is discharged: 100.0 100701 02/27/04 15:40:41 UPS returned from low battery condition: 100.0 100403 03/11/04 06:56:43 Self-test at UPS passed 100403 03/25/04 06:57:28 Self-test at UPS passed 300301 03/27/04 18:07:50 UPS battery is discharged: 100.0 100701 03/27/04 18:07:51 UPS returned from low battery condition: 100.0 100000 04/04/04 20:55:56 *** PowerChute PLUS Version 5.0 Started *** 100200 04/04/04 20:56:08 Communication established 100403 04/08/04 07:48:16 Self-test at UPS passed 300301 04/10/04 12:30:42 UPS battery is discharged: 100.0 100701 04/10/04 12:30:42 UPS returned from low battery condition: 100.0 300301 04/10/04 12:30:43 UPS battery is discharged: 100.0 100701 04/10/04 12:30:43 UPS returned from low battery condition: 100.0 300301 04/10/04 12:30:43 UPS battery is discharged: 100.0 100701 04/10/04 12:30:44 UPS returned from low battery condition: 100.0 300301 04/10/04 12:30:44 UPS battery is discharged: 100.0 100701 04/10/04 12:30:44 UPS returned from low battery condition: 100.0 300301 04/10/04 12:30:45 UPS battery is discharged: 100.0 100701 04/10/04 12:30:45 UPS returned from low battery condition: 100.0 300301 04/10/04 12:30:45 UPS battery is discharged: 100.0 100701 04/10/04 12:30:46 UPS returned from low battery condition: 100.0 100100 04/10/04 21:10:18 *** PowerChute PLUS Stopped *** 100000 04/10/04 21:49:25 *** PowerChute PLUS Version 5.0 Started *** 100200 04/10/04 21:49:41 Communication established 100100 04/10/04 22:00:50 *** PowerChute PLUS Stopped *** 100000 04/10/04 22:14:46 *** PowerChute PLUS Version 5.0 Started *** 100200 04/10/04 22:14:59 Communication established 100100 04/10/04 22:24:45 *** PowerChute PLUS Stopped *** 100000 04/10/04 22:28:52 *** PowerChute PLUS Version 5.0 Started *** 100200 04/10/04 22:29:05 Communication established 100100 04/10/04 22:33:34 *** PowerChute PLUS Stopped *** 100000 04/10/04 22:36:48 *** PowerChute PLUS Version 5.0 Started *** 100200 04/10/04 22:37:01 Communication established 100100 04/12/04 20:55:30 *** PowerChute PLUS Stopped *** 100000 04/12/04 20:58:44 *** PowerChute PLUS Version 5.0 Started *** 100200 04/12/04 20:58:59 Communication established 300301 04/21/04 15:29:56 UPS battery is discharged: 100.0 100701 04/21/04 15:29:57 UPS returned from low battery condition: 100.0 100403 04/22/04 07:48:17 Self-test at UPS passed 300301 04/23/04 09:17:58 UPS battery is discharged: 100.0 100701 04/23/04 09:18:00 UPS returned from low battery condition: 100.0 100403 04/25/04 18:45:45 Self-test at UPS passed 100100 05/05/04 21:21:11 *** PowerChute PLUS Stopped *** 100000 05/05/04 21:24:56 *** PowerChute PLUS Version 5.0 Started *** 100200 05/05/04 21:25:12 Communication established 100403 05/06/04 07:48:34 Self-test at UPS passed 100403 05/20/04 07:48:12 Self-test at UPS passed 100200 05/22/04 21:48:45 Communication established 301000 05/22/04 21:48:46 Check installation of Smart Cell signal cable 100200 05/22/04 21:50:24 Communication established 100100 05/22/04 21:54:40 *** PowerChute PLUS Stopped *** 100000 05/22/04 21:58:49 *** PowerChute PLUS Version 5.0 Started *** 100200 05/22/04 21:59:04 Communication established 200007 05/23/04 00:02:33 UPS on battery: Large momentary spike 122.8 V 100300 05/23/04 00:02:33 Normal power restored: UPS on line 200007 05/23/04 00:31:35 UPS on battery: Large momentary spike 123.5 V 100300 05/23/04 00:31:35 Normal power restored: UPS on line 200007 05/23/04 00:31:42 UPS on battery: Large momentary spike 122.8 V 100300 05/23/04 00:31:42 Normal power restored: UPS on line 200007 05/23/04 01:17:30 UPS on battery: Large momentary spike 122.8 V 100300 05/23/04 01:17:30 Normal power restored: UPS on line 200007 05/23/04 05:52:43 UPS on battery: Large momentary spike 122.8 V 100300 05/23/04 05:52:43 Normal power restored: UPS on line 200007 05/23/04 07:29:53 UPS on battery: Large momentary spike 123.5 V 100300 05/23/04 07:29:53 Normal power restored: UPS on line 200007 05/23/04 07:54:29 UPS on battery: Large momentary spike 122.8 V 100300 05/23/04 07:54:29 Normal power restored: UPS on line 200007 05/23/04 08:54:58 UPS on battery: Large momentary spike 120.2 V 100300 05/23/04 08:54:58 Normal power restored: UPS on line 200007 05/24/04 00:50:04 UPS on battery: Large momentary spike 122.8 V 100300 05/24/04 00:50:04 Normal power restored: UPS on line 200007 05/24/04 00:59:16 UPS on battery: Large momentary spike 122.8 V 100300 05/24/04 00:59:16 Normal power restored: UPS on line 200007 05/24/04 10:11:42 UPS on battery: Large momentary spike 122.2 V 100300 05/24/04 10:11:42 Normal power restored: UPS on line 200007 05/25/04 12:20:40 UPS on battery: Large momentary spike 122.2 V 100300 05/25/04 12:20:40 Normal power restored: UPS on line 100100 05/25/04 12:35:59 *** PowerChute PLUS Stopped *** 100000 05/25/04 12:44:37 *** PowerChute PLUS Version 5.0 Started *** 100200 05/25/04 12:44:53 Communication established 100100 05/25/04 18:44:39 *** PowerChute PLUS Stopped *** 100000 05/25/04 18:47:57 *** PowerChute PLUS Version 5.0 Started *** 100200 05/25/04 18:48:09 Communication established 200007 05/27/04 00:09:21 UPS on battery: Large momentary spike 122.8 V 100300 05/27/04 00:09:21 Normal power restored: UPS on line 200007 05/27/04 09:52:51 UPS on battery: Large momentary spike 122.2 V 100300 05/27/04 09:52:51 Normal power restored: UPS on line 200007 05/28/04 00:39:58 UPS on battery: Large momentary spike 124.1 V 100300 05/28/04 00:39:59 Normal power restored: UPS on line 200007 05/29/04 01:10:59 UPS on battery: Large momentary spike 122.8 V 100300 05/29/04 01:10:59 Normal power restored: UPS on line 200007 05/30/04 09:02:28 UPS on battery: Large momentary spike 122.2 V 100300 05/30/04 09:02:28 Normal power restored: UPS on line 200007 05/31/04 08:40:24 UPS on battery: Large momentary spike 122.2 V 100300 05/31/04 08:40:24 Normal power restored: UPS on line 100100 05/31/04 14:09:18 *** PowerChute PLUS Stopped *** 100000 05/31/04 14:12:52 *** PowerChute PLUS Version 5.0 Started *** 100200 05/31/04 14:13:10 Communication established 100100 06/02/04 08:38:30 *** PowerChute PLUS Stopped *** 100000 06/02/04 08:59:36 *** PowerChute PLUS Version 5.0 Started *** 100200 06/02/04 08:59:48 Communication established 100403 06/02/04 16:18:33 Self-test at UPS passed 200007 06/03/04 01:53:39 UPS on battery: Large momentary spike 120.9 V 100300 06/03/04 01:53:39 Normal power restored: UPS on line 200007 06/03/04 01:53:59 UPS on battery: Large momentary spike 120.9 V 100300 06/03/04 01:53:59 Normal power restored: UPS on line 200007 06/03/04 02:01:18 UPS on battery: Large momentary spike 122.2 V 100300 06/03/04 02:01:18 Normal power restored: UPS on line 100100 06/05/04 13:20:33 *** PowerChute PLUS Stopped *** 100000 06/05/04 13:24:13 *** PowerChute PLUS Version 5.0 Started *** 100200 06/05/04 13:24:24 Communication established 200007 06/07/04 00:40:46 UPS on battery: Large momentary spike 122.2 V 100300 06/07/04 00:40:46 Normal power restored: UPS on line 200007 06/07/04 23:59:29 UPS on battery: Large momentary spike 123.5 V 100300 06/07/04 23:59:29 Normal power restored: UPS on line 200007 06/08/04 00:10:49 UPS on battery: Large momentary spike 121.5 V 100300 06/08/04 00:10:49 Normal power restored: UPS on line 200007 06/08/04 00:44:19 UPS on battery: Large momentary spike 122.2 V 100300 06/08/04 00:44:19 Normal power restored: UPS on line 200007 06/09/04 00:39:14 UPS on battery: Large momentary spike 122.8 V 100300 06/09/04 00:39:14 Normal power restored: UPS on line 100100 06/09/04 21:02:45 *** PowerChute PLUS Stopped *** 100000 06/09/04 21:06:13 *** PowerChute PLUS Version 5.0 Started *** 100200 06/09/04 21:06:24 Communication established 200007 06/10/04 07:30:08 UPS on battery: Large momentary spike 126.1 V 100300 06/10/04 07:30:09 Normal power restored: UPS on line 200007 06/11/04 01:00:25 UPS on battery: Large momentary spike 123.5 V 100300 06/11/04 01:00:25 Normal power restored: UPS on line 200007 06/11/04 01:20:00 UPS on battery: Large momentary spike 122.8 V 100300 06/11/04 01:20:00 Normal power restored: UPS on line 200007 06/11/04 01:28:10 UPS on battery: Large momentary spike 122.8 V 100300 06/11/04 01:28:10 Normal power restored: UPS on line 200007 06/12/04 01:03:58 UPS on battery: Large momentary spike 122.2 V 100300 06/12/04 01:03:58 Normal power restored: UPS on line 200007 06/12/04 01:13:06 UPS on battery: Large momentary spike 121.5 V 100300 06/12/04 01:13:06 Normal power restored: UPS on line 200007 06/12/04 09:33:33 UPS on battery: Large momentary spike 120.9 V 100300 06/12/04 09:33:33 Normal power restored: UPS on line 200007 06/13/04 00:11:50 UPS on battery: Large momentary spike 121.5 V 100300 06/13/04 00:11:50 Normal power restored: UPS on line 200007 06/13/04 00:26:14 UPS on battery: Large momentary spike 120.9 V 100300 06/13/04 00:26:14 Normal power restored: UPS on line 200007 06/13/04 07:13:38 UPS on battery: Large momentary spike 122.8 V 100300 06/13/04 07:13:38 Normal power restored: UPS on line 200007 06/15/04 09:26:09 UPS on battery: Large momentary spike 123.5 V 100300 06/15/04 09:26:09 Normal power restored: UPS on line 100100 06/15/04 21:53:03 *** PowerChute PLUS Stopped *** 100000 06/15/04 22:11:14 *** PowerChute PLUS Version 5.0 Started *** 100200 06/15/04 22:11:26 Communication established 200007 06/16/04 10:19:51 UPS on battery: Large momentary spike 122.2 V 100300 06/16/04 10:19:51 Normal power restored: UPS on line 100403 06/16/04 16:18:56 Self-test at UPS passed 200007 06/17/04 00:49:22 UPS on battery: Large momentary spike 127.4 V 100300 06/17/04 00:49:22 Normal power restored: UPS on line 200007 06/17/04 07:50:10 UPS on battery: Large momentary spike 126.7 V 100300 06/17/04 07:50:10 Normal power restored: UPS on line 100403 06/30/04 16:18:40 Self-test at UPS passed 100100 07/11/04 22:49:42 *** PowerChute PLUS Stopped *** 100000 07/11/04 22:55:25 *** PowerChute PLUS Version 5.0 Started *** 100200 07/11/04 22:55:37 Communication established 100100 07/12/04 13:03:01 *** PowerChute PLUS Stopped *** 100000 07/12/04 13:08:58 *** PowerChute PLUS Version 5.0 Started *** 100200 07/12/04 13:09:12 Communication established 100403 07/14/04 16:18:46 Self-test at UPS passed 100100 07/18/04 11:27:13 *** PowerChute PLUS Stopped *** 100000 07/18/04 11:42:15 *** PowerChute PLUS Version 5.0 Started *** 100200 07/18/04 11:42:30 Communication established 100100 07/18/04 17:07:54 *** PowerChute PLUS Stopped *** 100000 07/18/04 17:11:01 *** PowerChute PLUS Version 5.0 Started *** 100200 07/18/04 17:11:22 Communication established